HeatWise HVAC HeatWise
HVAC Design

HVAC Software Comparison

Magnus Johnson
#HVAC#Design
Feature image

HVAC Software Comparison

Overview

In this post we’ll compare three different softwares for HVAC load calculations. We recently ran an internal study on this, and we wanted to share the results here. There are a lot of options on the market for load calculators, so hopefully this post helps you find one that makes sense for your team.

We’ll run the same inputs through each app and compare the load results. We’ll also dive into the usability and features of each app.

The three applications we’ll review are:

  1. Hourly Analysis Program (HAP) Version 6 by Carrier
  2. Chvac by EliteSoftware
  3. HeatWise by HeatWise-HVAC

Let’s get started.

Part 1 - Features & Usability

Firstly, each application has the user specify the building inputs a bit differently. Chvac and HeatWise were structured similarly in the sense that spaces are built by defining space attributes, envelope, internal loads, and other miscellaneous information, whereas HAP was structured very differently. It is also worth noting that HAP version 5 is structured very similarly to HeatWise and Chvac, but version 6 had some major changes. In HAP V6, space types are created and then applied to spaces that are built in the floor plan. The floor plans must be defined for the entire building by drawing out walls and partitions, placing windows, and assigning rooms to zones. These rooms can have space types applied to them.

Below are important features of each application:

HAP V6

  1. One great feature of HAP is the ability to select your location by using a world map and selecting a nearby weather station. This makes the process much easier and more refined for getting very accurate weather data.
  2. Another great feature is the ability to import a Revit model into the application. This makes the process of defining the floor plan very smooth when the project is being modeled in Revit. When the model changes, it can be re-uploaded into HAP to adjust the spaces as necessary.
  3. HAP has significant flexibility with the inputs. Weather data, building envelope, space types, and system details can all be configured with great detail, allowing for highly accurate simulations.

Chvac

  1. Possibly the best part about Chvac is how quick and easy it is to use. Building spaces and air handling units can be done very quickly, spaces can be copied and rotated, and the inputs are fairly simple.
  2. Default inputs can easily be set as overall project defaults, or as air handler defaults. So when a space is set to the general default or system default settings, the inputs can be copied over, saving time when building the model.
  3. Chvac does not include many of the unnecessary and overly complicated detailed inputs that HAP includes. This means far less time is spent trying to figure out details that may not end up making any difference in the end result.

HeatWise

  1. HeatWise was very simple to use, both in inputting data and reading through the results. Each input was obvious and the Quick Help bar on the side provided guidance throughout the process of creating spaces and systems. There is also plenty of reference data for easily obtaining inputs such as wall weights, lighting power density, and appliance loads.
  2. Since it’s entirely web based, HeatWise projects are constantly saved, and you can just exit your browser at any time and resume later from a different computer, making it easy to flip between home and work.
  3. HeatWise provides the option to request new weather data if your location isn’t available. There is also a feature to easily send feedback to the development team for assistance or questions about the software and how to use it.

Reading the Outputs

Reading through the outputs was a very different experience for each application. Chvac and HAP both provided more detailed results, and gave more flexibility in terms of what was reported. HeatWise provided less detail, but in a much simpler format that was easier to understand. HAP and Chvac gave PDF exports, whereas HeatWise provided results on the browser that could be accessed at any time, as well as a Microsoft Excel export.

Part 2 - Heating and Cooling Load Results

The results varied between the three applications. The highest cooling loads were seen in Chvac and the lowest were seen in HeatWise. However, between the three of them Chvac was the outlier, with HAP and HeatWise providing fairly similar results.

Example Project

The project studied was an existing 7-storey office building located in Vancouver, BC, Canada. The climate is mild in the winter with mild but humid summers. The building was built in 1970, made mostly of heavy concrete. Only one floor was modelled for this example, with one VAV air handling unit serving the entire floor. The floor was approximately 4500 ft2 with open office area, closed offices, boardrooms, and a lunch room.

Load comparison

Below is a summary of the total loads calculated from each application:

Table 1: Peak Loads by Application

ApplicationHeating Load (MBH)Sensible Cooling (MBH)Latent Cooling (MBH)Peak Airflow (CFM)
HAP31.6178.929.24027
HeatWise79.690.815.03192
Chvac85.9110.327.74933

1. The heat load was not provided for the whole system, but was only provided on a by-zone basis, therefore this result was calculated by adding up all heating loads. It was unclear if this would be the final actual heating load based on adjusted airflow values and whether or not it was including ventilation.

One noteworthy comparison between the three applications is the airflow and the latent cooling load. The tables below compares the time of the peak cooling, peak total cooling load, and peak airflow as reported by each application. For spaces that were internal, only a time of day was reported (without the month) because the time of year makes no difference for internal zones.

Table 2: Time of Peak Sensible Cooling Load by Zone

SpaceHeatWiseHAPChvac
Reception6pm June5pm June6am June
East Cubicles9am July9am July9pm June
West Cubicles9am July4pm June4pm June
Corridor4pm4pm7pm
Lunch Room11am August10am March10am September
South Cubicles10am September10am March10am September
South Offices3pm September2pm March3pm September
Large Boardroom4pm August4pm July4pm August

Table 3: Peak Sensible Cooling Load by Zone (MBH)

SpaceHeatWiseHAPChvac
Reception9.510.811.6
East Cubicles10.113.418.1
West Cubicles11.812.516.5
Corridor2.33.22.9
Lunch Room19.430.824.3
South Cubicles11.112.414.3
South Offices14.115.017.0
Large Boardroom14.015.216.4

Table 4: Peak Airflow by Zone (CFM)

SpaceHeatWiseHAPChvac
Reception433502542
East Cubicles480619842
West Cubicles539579768
Corridor15514664
Lunch Room88914261133
South Cubicles508573667
South Offices641694792
Large Boardroom639706764

The summary of peak sensible loads is shown in the image below: Image

Clearly there is a trend with Chvac estimating the highest loads, followed by HAP and then HeatWise, with the exception of the Lunch Room as an outlier where HAP estimated a much larger cooling load. There is generally more agreement between HeatWise and HAP. HAP is considered to be industry standard and most engineers have trust in its accuracy. Using HAP as a baseline, these results would suggest that both HeatWise and Chvac should be considered trustworthy as well.

Final Comments

HeatWise had a lower sensible load per zone than HAP, and therefore less airflow per zone and less airflow overall. Yet HeatWise had a higher sensible coil load than HAP, which seems counterintuitive. One explanation is that the simulation in HeatWise estimated 15% of wall loads as going into the ceiling plenum, as well as some portion of the lighting (see a description of why that may happen here: Plenum Load Impacts). This means that the spaces saw less total heat gain, and therefore required less air, resulting in a much lower airflow value. However, that heat still enters the system, but instead is manifested as a higher return air temperature, which is why the total sensible load is actually higher in HeatWise versus HAP.

The lower airflow also explains the discrepancy in coil latent loads, since the zones were assumed to be at 50% regardless of how much air was moving through them, so a lower airflow means less moisture being pulled out of the air.

Overall, HeatWise was much easier to use than the other applications, and load outputs were easier to analyse. Inputs such as building walls and windows seemed to correlate to similar wall R-values and Window U-values between all three apps. One major defect of Chvac was that SHGC values had to be entered manually for each different solar angle, whereas HeatWise and HAP only require one input and then generate the remainder of the values for varying angles.

← Back to Blog